| Notes |
| Date |
Text |
| 2023-02-15 13:11:03 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. REVIEW THE ONE-LINE DIAGRAM, WHICH IS SHOWING THE | | | 60A DISC CU-1 POWERED FROM THE ELECTRICAL METER AND | | | PANEL A SCHEDULE SHOWS A 60 AMPS BREAKER. NEC 215.5 | | | 2. A/C UNIT MAIN HOUSE - PANEL A SCHEDULE ONLY SHOWS | | | INFORMATION OF THE AIR HANDLER UNIT FEEDER. IT IS NOT | | | SHOWING INFORMATION OF THE A/C CONDENSER FEEDER AND | | | PROTECTION. NEC 408.4(A) | | | 3. PROVIDE INFORMATION OF THE EGC FOR THE PANEL PNL 'A' | | | 200A AND THE SUB PNL 'B' CABANA 60A POWERED FROM THE | | | PANEL PNL 'A' 200A. NEC 250.122 | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|