2023-02-15 13:11:03FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW THE ONE-LINE DIAGRAM, WHICH IS SHOWING THE
 60A DISC CU-1 POWERED FROM THE ELECTRICAL METER AND
 PANEL A SCHEDULE SHOWS A 60 AMPS BREAKER. NEC 215.5
 2. A/C UNIT MAIN HOUSE - PANEL A SCHEDULE ONLY SHOWS
 INFORMATION OF THE AIR HANDLER UNIT FEEDER. IT IS NOT
 SHOWING INFORMATION OF THE A/C CONDENSER FEEDER AND
 PROTECTION. NEC 408.4(A)
 3. PROVIDE INFORMATION OF THE EGC FOR THE PANEL PNL 'A'
 200A AND THE SUB PNL 'B' CABANA 60A POWERED FROM THE
 PANEL PNL 'A' 200A. NEC 250.122
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  