| 2023-01-05 09:09:45 | SEE GENERATOR PERMIT 22020100 |
| | |
| | 1ST REVIEW FMC |
| | PERMIT: 22020098 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE THE MUFFLER DETAILS INCLUDING THE MAX. |
| | DISTANCE OF THE EXHAUST PIPING AND PIPING SIZES. FBC |
| | 107.3.5 |
| | |
| | 2) PROVIDE A SITE PLAN INDICATING THE DISTANCE FROM |
| | GENERATOR EXHAUST TERMINATION LOCATION TO THE PROPERTY |
| | LINE. FMC 501.3.1 |
| | |
| | 3 IN DOING THE FUEL PORT AND PIPING REVIEW FOR THIS |
| | PROJECT I SEE THAT A REVISED SHEET M2.02G WAS SUBMITTED |
| | TO SHOW THE FUEL PIPING AND FUEL PORT. THERE IS A |
| | REVISION 10 ON THIS DRAWING THAT SHOWS A GEF-A AND |
| | GEF-B. I DO NOT SEE THESE ON THE APPROVED MASTER PERMIT |
| | APPROVED PLANS. PLEASE SUBMIT THE REVISION FOR THE |
| | ADDITION OF THESE EXHAUST FANS AND EXPLAIN THE REASON |
| | THEY WERE ADDED IN THIS REVISION. FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |