| Plan Review Notes For Permit 22120983 |
| Permit Number |
22120983 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-27 11:59:29 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. | | | NEC220. BUT FOR EACH SERVICE AND / OR FEEDER SUPPLYING | | | RECEPTACLES THAT PROVIDE SHORE POWER FOR BOAT, | | | ALSO APPLY THE DEMAND FACTORS OF TABLE 555.12 INSTEAD | | | OF THE DEMAND FACTORS OF 220.16(B). | | | 2. 100 AMPS PANEL SHALL BE PROVIDED WITH GROUND-FAULT | | | PROTECTION IN ACCORDANCE WITH 555.3 | | | 3. PROVIDE MINIMUM SIZE EQUIPMENT GROUNDING CONDUCTORS | | | FOR GROUNDING RACEWAY AND EQUIPMENT IN ACCORDANCE WITH | | | TABLE 250.122. | | | 4. PERMANENT SAFETY SIGNS SHALL BE INSTALLED TO GIVE | | | NOTICE OF ELECTRICAL SHOCK HAZARD RISKS TO PERSONS AS | | | PER ARTICLE 555.24 | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|