| 2023-03-15 10:34:52 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22120881 |
| | 3/15/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLUMBING AUDIT RESULTS. |
| | |
| | 1) SHEETS P101A & P101B: SEPARATE PERMIT APPLICATIONS |
| | AND PLAN SUBMITTALS ARE REQUIRED AT THIS TIME FOR THE |
| | POTABLE WATER BACKFLOW PREVENTERS AND THE GREASE |
| | INTERCEPTORS. IF YOU DO NOT CURRENTLY HAVE CONTRACTORS |
| | SELECTED AND PLANS FINALIZED FOR THESE ITEMS, YOU CAN |
| | SUBMIT APPLICATIONS- TBD (TO BE DETERMINED) BY EMAILING |
| | COMPLETED PERMIT APPLICATIONS TO |
| | [email protected]. YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE AUDIT STATUS TO PASS. |
| | |
| | PLEASE NOTE YOU HAVE THE OPTION OF SUBMITTING ONE |
| | APPLICATION FOR BOTH THE CONDO TOWER AND RENTAL TOWER |
| | BACKFLOW PREVENTERS, OR TWO IF PREFERRED. IT MAY BE A |
| | BETTER OPTION TO SUBMIT SEPARATE APPLICATIONS FOR THE |
| | CAFE INTERCEPTORS AND THE FUTURE TENANT INTERCEPTORS |
| | SINCE THE WORK MAY PROCEED ON DIFFERENT TIMELINES. |
| | CONCERNING THE INTERCEPTORS PLEASE REVIEW THE FOLLOWING |
| | DEFERRED SUBMITTAL REQUIREMENTS. |
| | A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF |
| | RECORD- SEC.1003.3. FBC P. |
| | B) EQUIPMENT SCHEDULE INDICATING THE MAKES AND MODELS |
| | AND CAPACITIES OF THE INTERCEPTORS. |
| | C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME |
| | A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, |
| | OR PDI G101- SEC. 1003.3.5 FBC P. |
| | D) ENLARGED PIPING DIAGRAM OR ISOMETRIC DRAWING SHOWING |
| | LOCATIONS AND SIZES OF INLETS, OUTLETS, VENTS, AND |
| | CLEANOUTS. PLEASE NOTE THE CITY OF WPB UTILITIES DEPT. |
| | REQUIRES A TWO-WAY CLEANOUT FOR USE AS A SAMPLING PORT. |
| | PLEASE PROVIDE A CLEANOUT DETAIL ON THE PLANS. |
| | E) ACCESS LID DETAILS INDICATING THE LIDS WILL BE HEAVY |
| | DUTY TRAFFIC RATED AND WILL BE EQUIPPED WITH ACCESS |
| | RESTRICTORS. HEAVY DUTY LIDS ARE ALSO REQUIRED FOR THE |
| | CLEANOUTS. |
| | |
| | 2) P101A & P101B: THE PLANS DO NOT SHOW THE BELOW SLAB |
| | SANITARY PIPING FOR THE BATHROOM FIXTURES, WASTE |
| | PIPING, LOCATIONS OF FLOOR DRAINS OR OTHER INDIRECT |
| | WASTE FIXTURES TO BE INSTALLED TYPICALLY IN THE PUMP |
| | ROOMS AND TRASH ROOMS; AND ELEVATOR SUMP PUMP PITS AND |
| | DISCHARGE PIPING RUNS AND DISPOSAL LOCATIONS- SEC. |
| | 107.2.1 WPB. |
| | A) CONCERNING THE FLOOR DRAINS, IF TRAP PRIMERS ARE TO |
| | BE INSTALLED PLEASE SHOW THE WATER PIPING CONNECTION |
| | LOCATIONS- SEC. 1002.4.1.1. FBC P. |
| | |
| | 3) P101A & P101B: PROVIDE A SANITARY DRAINAGE AND VENT |
| | ISOMETRIC DRAWING FOR THE BELOW FLOOR SLAB PLUMBING |
| | INCLUDING THE GREASE WASTE PIPING SYSTEM- SECS. 107.2.1 |
| | WPB & 107.3.5.1.3 WPB. |
| | |
| | 4) P101A: PLEASE SHOW THE GREASE WASTE AND SANITARY |
| | PIPE SIZES ON THE DRAWINGS- TABLE 710.1(1) FBC P. |
| | |
| | 5) P-101.1A: THE PLAN SHOWS UNIDENTIFIED PIPING RUNNING |
| | BETWEEN THE DPR PUMP ROOM AND THE BUILDING EXTERIOR. |
| | PLEASE LABEL THE TYPES AND SIZES OF PIPING- SEC. |
| | 107.2.1 WPB. CLARIFY IF ANY OF THE PIPING IS BELOW THE |
| | SLAB. CONCERNING THE ABOVE CEILING GAS PIPING ON THE |
| | EAST SIDE OF THE BUILDING, SEE COMMENT #6 BELOW. |
| | |
| | 6) SHEET P-101.1B IS NOT NECESSARY FOR THIS FOUNDATION |
| | ONLY PERMIT BECAUSE IT SHOWS GAS METERS AND GAS PIPING |
| | RUNS ABOVE THE FIRST FLOOR CEILINGS. NO WORK SHOWN ON |
| | THE PLANS WILL BE PERMITTED UNDER THIS FOUNDATION ONLY |
| | PERMIT, AND THE PLAN WILL BE LOCKED OUT AT TIME OF |
| | PLUMBING PLAN APPROVAL- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |