Plan Review Notes
Plan Review Notes For Permit 22120781
Permit Number 22120781
Review Stop B
Sequence Number 1
Notes
Date Text
2022-12-29 15:41:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 105.13 SUBMIT AN APPLICATION FOR THE FUEL TANK.
 YOU DO NOT NEED TO UPLOAD PLANS OR HAVE A CONTRACTOR AT
 THIS TIME.
  
 2. FBC 107.2.5, SUBMIT A SITE PLAN SHOWING LOCATION OF
 PROPOSED PAD, INCLUDING THE FLOOD ZONE LINES. IF
 LOCATED IN A FLOOD ZONE THE TANKS WILL BE REQUIRED TO
 EITHER BE DESIGNED TO RESIST FLOOD LOADS OR THE SLAB
 WILL BE REQUIRED TO BE ELEVATED TO BASE FLOOD OR ABOVE.
 FBC B 1609, 1622.
  
 3. FBC B CHAPTER 16, PROPOSED TANKS WILL BE REQUIRED TO
 RESIST WIND LOADS AND POSSIBLY FLOOD LOADS DEPENDING ON
 LOCATION AND ELEVATION. WHEN RESUBMITTING, CONFIRM THAT
 THE ANCHORING OF THE TANKS WILL BE INCLUDED IN THE FUEL
 PERMIT INFORMATION.
  
  