| Plan Review Notes For Permit 22120781 |
| Permit Number |
22120781 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-29 15:41:53 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 105.13 SUBMIT AN APPLICATION FOR THE FUEL TANK. | | | YOU DO NOT NEED TO UPLOAD PLANS OR HAVE A CONTRACTOR AT | | | THIS TIME. | | | | | | 2. FBC 107.2.5, SUBMIT A SITE PLAN SHOWING LOCATION OF | | | PROPOSED PAD, INCLUDING THE FLOOD ZONE LINES. IF | | | LOCATED IN A FLOOD ZONE THE TANKS WILL BE REQUIRED TO | | | EITHER BE DESIGNED TO RESIST FLOOD LOADS OR THE SLAB | | | WILL BE REQUIRED TO BE ELEVATED TO BASE FLOOD OR ABOVE. | | | FBC B 1609, 1622. | | | | | | 3. FBC B CHAPTER 16, PROPOSED TANKS WILL BE REQUIRED TO | | | RESIST WIND LOADS AND POSSIBLY FLOOD LOADS DEPENDING ON | | | LOCATION AND ELEVATION. WHEN RESUBMITTING, CONFIRM THAT | | | THE ANCHORING OF THE TANKS WILL BE INCLUDED IN THE FUEL | | | PERMIT INFORMATION. | | | | | | |
|