Plan Review Notes
Plan Review Notes For Permit 22120772
Permit Number 22120772
Review Stop B
Sequence Number 1
Notes
Date Text
2022-12-22 13:42:54NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE SINGLE HUNG WINDOWS, FRONT
 DOOR, FRONT DOOR SIDE LITES, FIXED GLASS WINDOWS.
  
 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB
 107.3.4
  
 3) PLEASE PROVIDE THE FRONT PAGE OF THE PRODUCT
 APPROVAL FOR THE "ALUMINUM BIFOLD DOOR".
  
 4) INSTALLATION DRAWINGS ARE PROVIDED FOR AWNING
 WINDOWS - PLEASE SHOW THE LOCATION AND SIZES FOR THE
 AWNING WINDOWS.
  
 5) PLEASE PROVIDE THE FRONT PAGES OF THE PRODUCT
 APPROVAL FOR THE AWNING WINDOW.
  
 6) FBC R320.1.1
 ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES, TRIPLEXES,
 CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT LEAST ONE
 BATHROOM, LOCATED WITH MAXIMUM POSSIBLE PRIVACY, WHERE
 BATHROOMS ARE PROVIDED ON HABITABLE GRADE LEVELS, WITH
 A DOOR THAT HAS A 29-INCH (737 MM) CLEAR OPENING.
 HOWEVER, IF ONLY A TOILET ROOM IS PROVIDED AT GRADE
 LEVEL, SUCH TOILET ROOMS SHALL HAVE A CLEAR OPENING OF
 NOT LESS THAN 29 INCHES (737 MM).
  
 7) PLEASE CIRCLE THE ROOF TILE ATTACHMENT IN THE
 PROVIDED PRODUCT APPROVAL (17-1221.05). IF USING
 ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL.
  
 8) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT
 DECK (17-1004.09) - PLEASE CIRCLE THE ROOFING SYSTEM TO
 BE USED IN THE ROOFING PRODUCT APPROVAL - ROOFING
 SYSTEM TO BE USED ON THE PROVIDED PRODUCT APPROVAL MAY
 REQUIRE ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS
 FROM AN ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND
 3 WHICH REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM
 SHOWN ON THE PRODUCT APPROVAL - SEE GENERAL LIMITATION
 NOTE NUMBER 7 ON THE PRODUCT APPROVAL.
  
 9) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).