Plan Review Notes
Plan Review Notes For Permit 22120742
Permit Number 22120742
Review Stop B
Sequence Number 3
Notes
Date Text
2023-01-19 10:24:53JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL36904.1-R7 MAXIMUM DESIGN PRESSURE -101.25
 PSF. DO NOT MEET THE MINIMUM ZONE 3 DESIGN PRESSURE
 REQUIREMENT OF -102 FOR EXPOSURE CATEGORY C AREAS WITH
 A GABLE ROOF; ROOF SLOPES 5/12-6/12 MEAN ROOF HEIGHT UP
 TO 15 FT. SELECT SYSTEM THAT MEETS OR EXCEEDS THIS
 REQUIREMENT. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY
 COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC
 ENGINEERING.
 2. FBC B 107.2.1. PLEASE VERIFY: SUBMITTED ROOF DIAGRAM
 INDICATES ROOF SLOPE OF 5/12; GOOGLE EARTH IMAGE
 APPEARS TO SHOW ROOF SLOPE LESS THAN 5/12. IF LESS THAN
 5/12 THE MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT IS
 -121 FOR EXPOSURE CATEGORY C AREAS WITH A GABLE ROOF;
 ROOF SLOPES 2/12-4/12 MEAN ROOF HEIGHT UP TO 15 FT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  