| 2022-12-16 07:58:10 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-22120711 | | | 12/16/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SUBMIT A MANUFACTURER???S SPEC SHEET FOR THE | | | BACKFLOW PREVENTER THAT INDICATES THE MAKE AND MODEL OF | | | THE DEVICE AND THAT IT IS LEAD-FREE AND ON THE APPROVED | | | DEVICE LIST PUBLISHED BY THE UNIVERSITY OF SOUTHERN | | | CALIFORNIA- WPB UTILITIES CROSS-CONNECTION MANUAL. | | | PLEASE NOTE A REDUCED PRESSURE PRINCIPLE BACKFLOW | | | PREVENTER IS REQUIRED FOR POTABLE WATER SERVICES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|