Plan Review Notes
Plan Review Notes For Permit 22120701
Permit Number 22120701
Review Stop SIGNATURE
Sequence Number 2
Notes
Date Text
2023-01-10 14:17:532ND SIGNATURE REVIEW.
 1/10/23
  
 THE HAND DRAWN PLUMBING DETAILS PREPARED BY THE
 CONTRACTOR CANNOT BE PLACED ON THE LICENSED ENGINEER'S
 APPROVED ELECTRICAL PLAN. PLANS SUBMITTED
 FOR PERMITTING AND PUBLIC RECORD THAT BEAR A FL.
 LICENSED ENGINEEER'S TITLE BLOCK SHALL BE DIGITALLY
 SIGNED AND SEALED BY THE ENGINEER PER FL. STATUTE
 471..025 & SEC. 61G15-23.005 FAC. THE CONTRACTOR SHALL
 PROVIDE HIS OWN PLAN FOR THE PROPOSED PROJECT- FL
 STATUTE 471.003(2)(H) & 471.025.
  
 CHRISTOPHER L. COLE
 401 CLEMATIS C STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 MECHANICAL/PLUMBING PLANS EXAMINER
 [email protected]
  
  
 1ST SIGNATURE REVIEW FAILED
  
 1) PLAN SUBMITTED DETAILS A PE TITLE BLOCK WITHOUT THE
 REQUIRED SIGNATURE AN SEAL.. PLEASE CORRECT AS OUTLINED
 BELOW
  
 .
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  