| Notes |
| Date |
Text |
| 2022-12-19 12:51:04 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 2210701 | | | 12/19/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A2: THE PLAN SHEET IS FAILED BECAUSE IT IS AN | | | ENGINEER' S PLAN THAT HAS BEEN COPIED AND MARKED UP BY | | | THE CONTRACTOR. THE APPLICANT CAN EITHER SUBMIT A | | | DRAWING PREPARED AND SIGNED BY THE PLUMBING CONTRACTOR, | | | OR HAVE THE ENGINEER PROVIDE A REVISED DIDITALLY SIGNED | | | AND SEALED PLAN WITH THE NEW DETAILS- SECTION 107.2.1 | | | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. | | | | | | 2) A2: THE APPLICATION INDICATES A GARBAGE DISPOSAL | | | WILL BE INSTALLED HOWEVER THE DISPOSAL IS NOT NOTED ON | | | THE PLAN- SEC. 107.2.1 WPB. PLEASE NOTE THAT THE | | | DISPOSAL SHALL DISCHARGE INTO A SOLIDS INTERCEPTOR | | | PRIOR TO DRAINING INTO THE GREASE INTERCEPTOR- SEC. | | | 1003.3.2 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|