Plan Review Notes
Plan Review Notes For Permit 22120701
Permit Number 22120701
Review Stop E
Sequence Number 1
Notes
Date Text
2022-12-27 14:32:32ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE ELECTRICAL PLANS DETAILING ELECTRICAL
 OUTLETS TO BE INSTALLED, INCLUDE CONDUCTOR SIZES, GFI
 PROTECTION, AND PANEL SCHEDULE AS APPLICABLE. NEC 215.5
 AND NEC 210.8(B)(5)
 2) PLAN SUBMITTED DETAILS A PE TITLE BLOCK WITHOUT THE
 REQUIRED SIGNATURE AN SEAL.SEE SIGNATURE REVIEW
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  