| 2023-05-15 14:37:14 | SFR ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | 4TH REVIEW |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW THE REQUIRED ROOF VENTILATION (SOFFIT |
| | VENTS) - R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN OR SNOW. |
| | |
| | 2) A SMOKE DETECTOR IS REQUIRED IN THE HALLWAY NEAR THE |
| | BEDROOMS - FBC R314.3 LOCATION. SMOKE ALARMS SHALL BE |
| | INSTALLED IN THE FOLLOWING LOCATIONS: |
| | |
| | A).IN EACH SLEEPING ROOM. |
| | |
| | B).OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | |
| | C).ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL |
| | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| | |
| | D).SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET |
| | (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A |
| | BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS |
| | WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY |
| | SECTION R314.3. |
| | |
| | 3) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT |
| | DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN |
| | THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE |
| | USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE |
| | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN |
| | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH |
| | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE |
| | PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE |
| | PRODUCT APPROVAL. |
| | |
| | 4) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) - |
| | PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE |
| | PRODUCT APPROVAL. |
| | |
| | 5) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857) |
| | - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE |
| | PRODUCT APPROVAL. |
| | |
| | |
| | |
| | |