| 2023-04-03 15:58:58 | THE ENERGY CALCULATIONS SUBMITTED THIS CYCLE IS FOR THE | | | ENTIRE HOUSE WHICH IS 1472 SQUARE FEET. THE MECHANICAL | | | DRAWING SHOWS THE NEW MECHANICAL SYSTEM IS FOR THE | | | ADDITION ONLY. PROVIDE AN ENERGY CALCULATION FOR THE | | | NEW ADDITION ONLY. | | | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS THAT WERE | | | ASKED FOR IN THE FIRST CYCLE REVIEW WAS NOT SUBMITTED. | | | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS ADDITION. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|