2023-02-06 12:26:30FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW EXISTING MAIN PANEL "A" SCHEDULE PROVIDED
 (VA, TRIP, WIRE) TO BE IN ACCORDANCE WITH NEC 220, 240,
 310.15(B)(16)
  
 2. PROVIDE MAIN PANEL SCHEDULE WITH EXISTING AND NEW
 LOAD ALONG WITH THE LOAD CALCULATION. NEC 220, NEC
 408.4(A)
  
 3. PROVIDE INFORMATION OF THE SERVICE. NEC 230
  
 4. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON
 MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315
  
 5. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11
 THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION
 FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS
 APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING
 OCCUPANCIES
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  