Plan Review Notes
Plan Review Notes For Permit 22120680
Permit Number 22120680
Review Stop B
Sequence Number 1
Notes
Date Text
2023-02-23 09:21:00SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE REQUIRED ROOF VENTILATION - R806.1
 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW.
  
 2) DRAWING SP-1 THE INCORRECT DOOR SIZE IS SHOWN ON THE
 DOOR SCHEDULE - PLEASE CORRECT.
  
 3) PLEASE SHOW THE REQUIRED SMOKE DETECTOR LOCATIONS -
 FBC R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 4) PLEASE SHOW THE EXTERIOR WINDOW AND DOOR FLASHING -
 FBC R703.1.1 WATER RESISTANCE.
 THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND
 CONSTRUCTED IN A MANNER THAT PREVENTS THE ACCUMULATION
 OF WATER WITHIN THE WALL ASSEMBLY BY PROVIDING A
 WATER-RESISTANT BARRIER BEHIND THE EXTERIOR CLADDING AS
 REQUIRED BY SECTION R703.2 AND A MEANS OF DRAINING TO
 THE EXTERIOR WATER THAT PENETRATES THE EXTERIOR
 CLADDING.
 EXCEPTIONS: 1. A WEATHER-RESISTANT EXTERIOR WALL
 ENVELOPE SHALL NOT BE REQUIRED OVER CONCRETE OR MASONRY
 WALLS DESIGNED IN ACCORDANCE WITH CHAPTER 6 AND FLASHED
 IN ACCORDANCE WITH SECTION R703.4.
  
 5) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT
 DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN
 THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE
 USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE
 ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN
 ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH
 REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE
 PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE
 PRODUCT APPROVAL.
  
 6) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) -
 PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
 7) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857)
 - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
 8) PLEASE SHOW THE EXISTING FLOOR PLAN - SHOWING THE
 USE FOR EACH ROOM - THE NEW ADDITION CANNOT BLOCK AN
 EMERGENCY EGRESS FOR AN EXISTING BEDROOM - FBC R310.1
 EMERGENCY ESCAPE AND RESCUE OPENING REQUIRED.
 BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM
 SHALL HAVE NOT LESS THAN ONE OPERABLE EMERGENCY ESCAPE
 AND RESCUE OPENING.