| Date |
Text |
| 2023-02-23 09:21:00 | SFR ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW THE REQUIRED ROOF VENTILATION - R806.1 |
| | VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN OR SNOW. |
| | |
| | 2) DRAWING SP-1 THE INCORRECT DOOR SIZE IS SHOWN ON THE |
| | DOOR SCHEDULE - PLEASE CORRECT. |
| | |
| | 3) PLEASE SHOW THE REQUIRED SMOKE DETECTOR LOCATIONS - |
| | FBC R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 4) PLEASE SHOW THE EXTERIOR WINDOW AND DOOR FLASHING - |
| | FBC R703.1.1 WATER RESISTANCE. |
| | THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND |
| | CONSTRUCTED IN A MANNER THAT PREVENTS THE ACCUMULATION |
| | OF WATER WITHIN THE WALL ASSEMBLY BY PROVIDING A |
| | WATER-RESISTANT BARRIER BEHIND THE EXTERIOR CLADDING AS |
| | REQUIRED BY SECTION R703.2 AND A MEANS OF DRAINING TO |
| | THE EXTERIOR WATER THAT PENETRATES THE EXTERIOR |
| | CLADDING. |
| | EXCEPTIONS: 1. A WEATHER-RESISTANT EXTERIOR WALL |
| | ENVELOPE SHALL NOT BE REQUIRED OVER CONCRETE OR MASONRY |
| | WALLS DESIGNED IN ACCORDANCE WITH CHAPTER 6 AND FLASHED |
| | IN ACCORDANCE WITH SECTION R703.4. |
| | |
| | 5) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT |
| | DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN |
| | THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE |
| | USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE |
| | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN |
| | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH |
| | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE |
| | PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE |
| | PRODUCT APPROVAL. |
| | |
| | 6) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) - |
| | PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE |
| | PRODUCT APPROVAL. |
| | |
| | 7) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857) |
| | - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE |
| | PRODUCT APPROVAL. |
| | |
| | 8) PLEASE SHOW THE EXISTING FLOOR PLAN - SHOWING THE |
| | USE FOR EACH ROOM - THE NEW ADDITION CANNOT BLOCK AN |
| | EMERGENCY EGRESS FOR AN EXISTING BEDROOM - FBC R310.1 |
| | EMERGENCY ESCAPE AND RESCUE OPENING REQUIRED. |
| | BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM |
| | SHALL HAVE NOT LESS THAN ONE OPERABLE EMERGENCY ESCAPE |
| | AND RESCUE OPENING. |