| Plan Review Notes For Permit 22120627 |
| Permit Number |
22120627 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-15 09:40:23 | FIRE REVIEW COMMENTS: | | | | | | THIS SUBMITTAL WAS REVIEWED AND FAILED FOR THE | | | FOLLOWING. | | | | | | (1) NO DEVICE COUNT WAS PROVIDED TO INDICATE NUMBER OF | | | DEVICES AND LOCATIONS. | | | | | | (2) THE DEVICE LOCATIONS WERE NOT INCLUDED TO DETERMINE | | | ADEQUATE COVERAGE AREA (FLOOR PLAN). | | | | | | | | | (3) BATTERY CALCULATIONS WERE NOT SUBMITTED TO INDICATE | | | FIRE ALARM PANEL CAN SUPPORT PROPOSED DEVICES. | | | | | | (4) PROVIDE A SEQUENCE OF OPERATION AS TO HOW DEVICES | | | WILL REPORT TO THE PANEL. | | | | | | | | | (5) RESUBMITTAL MAY GENERATE ADDITIONAL COMMENTS. | | | | | | NFPA 1, 1.14 | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|