Plan Review Notes
Plan Review Notes For Permit 22120570
Permit Number 22120570
Review Stop B
Sequence Number 2
Notes
Date Text
2023-02-27 16:07:16PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVAL PENDING APPROVAL OF SIGNATURE
 REVIEW.
  
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. THE ENGINEER'S LETTER IDENTIFIED AS "PV14 LETTER
 BRADLEY" LOCATED WITHIN THE SUPPORTING DOCUMENTS
 APPEARS TO BE A SCAN OF AN ORIGINAL ENGINEER HAND
 SIGNED/SEALED LETTER.
  
 A. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND
 SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A
 VALID DIGITAL SIGNATURE.
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C.
 B. PLEASE SUBMIT ENGINEER'S LETTER WITH A VALID DIGITAL
 SIGNATURE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 2. FBC B TABLE 1604.5 & FBC B 1609. THE WIND LOAD SHOWN
 ON THE ENGINEER'S LETTER, IDENTIFIED AS "PV14 LETTER
 BRADLEY", IS FOR 169 MPH. THIS APPEARS TO BE FOR A RISK
 CATEGORY 2. AS PER THE FLORIDA BUILDING CODE THE WIND
 LOAD, WITHIN THE ENGINEER'S LETTER, NEEDS TO BE
 ADJUSTED TO 170 MPH.
  