| | BUILDING REVIEW APPROVAL PENDING APPROVAL OF SIGNATURE |
| | REVIEW. |
| | |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| | |
| | 1. THE ENGINEER'S LETTER IDENTIFIED AS "PV14 LETTER |
| | BRADLEY" LOCATED WITHIN THE SUPPORTING DOCUMENTS |
| | APPEARS TO BE A SCAN OF AN ORIGINAL ENGINEER HAND |
| | SIGNED/SEALED LETTER. |
| | |
| | A. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND |
| | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A |
| | VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND |
| | SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A |
| | VALID DIGITAL SIGNATURE. |
| | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR |
| | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH |
| | 61G1-16 AND 61G15, F.A.C. |
| | B. PLEASE SUBMIT ENGINEER'S LETTER WITH A VALID DIGITAL |
| | SIGNATURE. |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. |
| | 481, F.S. & 61G1. |
| | |
| | 2. FBC B TABLE 1604.5 & FBC B 1609. THE WIND LOAD SHOWN |
| | ON THE ENGINEER'S LETTER, IDENTIFIED AS "PV14 LETTER |
| | BRADLEY", IS FOR 169 MPH. THIS APPEARS TO BE FOR A RISK |
| | CATEGORY 2. AS PER THE FLORIDA BUILDING CODE THE WIND |
| | LOAD, WITHIN THE ENGINEER'S LETTER, NEEDS TO BE |
| | ADJUSTED TO 170 MPH. |
| | |