| Plan Review Notes For Permit 22120561 |
| Permit Number |
22120561 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-02-27 15:39:06 | ADJUST THE OUTDOOR AIR CALCULATION FOR THE LOBBY. A | | | LOBBY IS 150 OCCUPANTS PER 1000 SQ. FT. X 5 CFM PER | | | OCCUPANT + SQ. FT. X .06 FOR SPACE CFM. THE OCCUPANT | | | COUNT FOR THIS SPACE IS 25 OCCUPANTS. FMC 403.3.1.1 AND | | | TABLE 403.3.1.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|