| Plan Review Notes For Permit 22120561 |
| Permit Number |
22120561 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-06 08:08:49 | 1ST REVIEW FMC | | | PERMIT: 22120561 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS NEW | | | BUILDING. FEC C401.2 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS NEW BUILDING. FEC C403.2.1 | | | | | | 3) SHEET M-100: PROVIDE THE OUTDOOR AIR DUCT SIZE FOR | | | AHU-1. FBC 107.3.5 | | | | | | 4) SHEET M-102: SHOW GUARD PROTECTION FOR ALL EQUIPMENT | | | ON THE ROOF THAT IS WITHIN 10 FEET FROM THE ROOF EDGE. | | | FMC 304.11 | | | | | | 5) SHEET M-600: THE 168 SQ. FT. LOBBY WOULD ACCOMMODATE | | | 26 OCCUPANTS AND REQUIRE 140 CFM???S OF OUTDOOR AIR, | | | PLEASE MODIFY THE SCHEDULES TO MEET THIS REQUIREMENT. | | | FMC 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|