| 2023-01-10 07:58:06 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22120561 |
| | ADD: 915 N. RAILROAD AVE. |
| | CONT: HEDRICK BROTHERS CONSTRRUCTION |
| | TEL: 561-308-2954 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 04TH/2023 |
| | ACTION: DENIED |
| | |
| | 1) SHEET T100 TITLE SHEET: |
| | 1A) PROJECT DESCRIPTION THE EXISTING BUILDING IS |
| | DEMOLISHED WITH EXCEPTION OF THE NORTH AND OR SOUTH |
| | WALLS TO REMAIN. NEW BUILDING IS PROPOSED IN ITS PLACE. |
| | 2020 EXISTING BUILDING CODE SECTION 907.4.1. |
| | (ALTERATION LEVEL LLL ALTERATION) EVALUATION AND |
| | ANALYSIS. AN ENGINEERING EVALUATION AND ANALYSIS THAT |
| | ESTABLISHES THE STRUCTURAL ADEQUACY OF THE ALTERED |
| | STRUCTURE SHALL BE PREPARED BY A REGISTERED DESIGN |
| | PROFESSIONAL AND SUBMITTED TO THE CODE OFFICIAL. HOW |
| | WILL THE 2 STORY SIDE WALLS AND FOOTER BE KEPT FROM |
| | OVERTURNING DURING CONSTRUCTION. EVERY STRUCTURE SHALL |
| | BE DESIGNED TO RESIST THE OVERTURNING POSITIVE & |
| | NEGATIVE EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED |
| | IN THIS CHAPTER. SEE SECTION 1609 FOR WIND LOADS. |
| | |
| | 1B) 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL |
| | NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1C) BUILDING PROVISO: DEFERRED SUBMITTALS: |
| | COMPONENTS & CLADDING. |
| | (A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: CURTAINWALL, STOREFRONTS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS |
| | (E) PRE-ENGINEERED ROOFTOP A/C STANDS |
| | STAIR & ELEVATOR SHOP DRAWINGS |
| | ROOF ACCESS LADDER SHOP DRAWINGS |
| | FRONT CANOPY SHOP DRAWINGS |
| | STEEL SHOP DRAWINGS |
| | |
| | 1D) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY |
| | FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF |
| | APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 1E) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS. |
| | PLEASE IDENTIFY IN THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| | UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE AND |
| | SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| | SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| | USED IN THE TESTS. |
| | |
| | |
| | 2) SHEET S001 GENERAL NOTES: GEOTECHNICAL INVESTIGATIVE |
| | REPORT. PLEASE PROVIDE THE ENGINEERING REPORT LISTED BY |
| | UNIVERSAL ENGINEERING SCIENCES, DATED FEB. 07TH, 2022. |
| | 2020 FBC-BUILDING 1803.5.2 QUESTIONABLE SOIL. |
| | |
| | 3) SHEET S002 GENERAL NOTES: |
| | 3A) WELDING. WELDED OR BOLTED CONNECTIONS. THIS |
| | BUILDING CONTAINS EITHER BOLTED AND OR WELDED |
| | CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD |
| | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD |
| | BRUNELLE AT 561-805-6670. |
| | |
| | 3B) PLYWOOD ROOF SHEATHING NOTE LIST THE USE OF PLYWOOD |
| | ROOF SHEATHING. NOTE THIS IS A CONSTRUCTION TYPE LL-B |
| | BUILDING TYPE. THE 2020 FBC-BUILDING CODE SECTION |
| | 603.1.1.3 FIRE RETARDANT TREATED WOOD SHALL BE |
| | PERMITTED IN ROOF CONSTRUCTION INCLUDING GIRDERS, |
| | FRAMING AND DECKING. |
| | |
| | 4) SHEET A101: |
| | 4A) THE FLOOR PLAN SHOWS TWO OUTSWING DOORS, IT APPEARS |
| | THAT THEY SWING OUT OVER THE PROPERTY LINE AND INTO THE |
| | RIGHT-OF-WAY. SEE SECTION 3202.2 2020 FBC-BUILDING |
| | CODE. SEE SURVEY IT APPEARS THE PROPERTY LINE IS THE |
| | FRONT OF THE BUILDING. |
| | |
| | 4B) THE SAME ISSUE APPEARS WITH S2 THE STOREFRONT DOOR |
| | SYSTEM, THE PLAN DOES NOT INDICATE IF THE DOORS WILL |
| | FOLD OUT OVER THE PROPERTY LINE OR BACK INTO THE |
| | BUILDING, ADDITIONAL INFORMATION IS REQUIRED FOR CODE |
| | COMPLIANCE, 3202.2 2020 FBC-BUILDING CODE. SHEET A601 |
| | DETAIL NOT HELPFUL. CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 5) SHEET LS101 & LS102 THE 3 FEET WIDE EXIT DOORS ARE |
| | TAKING A CLEAR WIDTH OF 35 INCHES OR 178 OCCUPANTS. |
| | 2020 ACCESS. CODE 404.2.3. CLEAR WIDTH & SIZE OF DOORS, |
| | 2020 FBC-B 1010.1.1. THE MINIMUM SIZE OF A SWING DOORS |
| | IS MEASURED CLEAR OPENING OF THE DOORWAY WITH THE |
| | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF |
| | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
| | 34INCHES/ 0.20= 170 OCCUPANTS NOT THE 178. PLEASE |
| | ADDRESS CLEAR WIDTH OF ALL EGRESS DOORS. |
| | |
| | 6) SHEET A401 FRONT & REAR ELEVATIONS. THE FRONT |
| | ELEVATION SHOWS THE CITY SIDEWALK RAMPED UP TO MEET |
| | YOUR NEW FINISH FLOOR LEVEL, IT APPEARS THE CITY |
| | SIDEWALK IS RAISED AND ADDITIONAL 6 INCHES AT THE NEW |
| | DOORWAYS, PLEASE PROVIDE WHY THIS OCCURS WITH A NEW |
| | CONSTRUCTION ON THE EAST AND WEST WALLS? 2020 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.2.1. |
| | CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| | INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 7) SHEET A301: |
| | 7A) THE ROOF PLAN SHOWS THE USE OF A ROOF HATCH AND |
| | DETAIL TO GAIN ACCESS ONTO THE ROOF. THE ROOF HATCH |
| | SHOWS A CLEAR OPENING OF 3X3=9 SQ. FT. PLEASE REVIEW IN |
| | THE 2020 FBC-BUILD CODE SECTION 1011.12.2 ROOF ACCESS |
| | THE EXCEPTION, THE ROOF HATCH SHALL NOT BE LESS THAN 16 |
| | SQ. FT. IN AREA AND HAVING A MINIMUM DIMENSION OF 2 |
| | FEET. |
| | |
| | 7B) ROOF OVERFLOW SCUPPERS ARE SHOWN DETAIL GIVEN |
| | 5/A-303 BUT NEITHER PROVIDE THE MINIMUM WIDTH AND |
| | HEIGHT IN ACCORDANCE WITH 1503.4.1 THE SIZING AND |
| | INSTALLATION OF THE SECONDARY OVERFLOW IN ACCORDANCE |
| | WITH FBC-PLUMBING CODE CHAPTER 11. |
| | |
| | 8) SHEET A502: |
| | 8A) SHOWS A CUT SECTION THROUGH THE ELEVATOR SHAFT AND |
| | ELEVATOR PIT. THIS DETAIL SHOWS THE BOTTOM OF THE |
| | ELEVATOR PIT BOTTOM OF FOUNDATION BELOW 5 FEET BELOW |
| | FINISH FLOOR AND DEEPER POSSIBLY ANOTHER 2 FEET 6 |
| | INCHES FOR THE BOTTOM GRADE FOR THE SUMP PIT. NOTE |
| | STATES THE GC SHALL HIRE A LICENSED SHORING ENGINEER TO |
| | TEMPORARY SUPPORT THE EXISTING WALL OF 905/ AND 915. |
| | SHOW COMPLIANCE WITH BOTH SECTIONS 1803.5.7 & 1804.2.1. |
| | THE UNDERPINNING SEQUENCE OF INSTALLATION SHALL BE |
| | IDENTIFIED AND INSTALLED IN ACCORDANCE WITH APPROVED |
| | CONSTRUCTION DOCUMENTS. 2020 FBC-BUILDING. |
| | |
| | 8B) THE ELEVATOR SECTION SHOWS THE USE OF UNDERGROUND |
| | HYDRAULIC ELEVATOR CYLINDER. PLEASE PROVIDE COMPLIANCE |
| | WITH THE 2020 FBC-BUILDING CODE SECTION |
| | 3011.1.1-3011.1.3. |
| | |
| | 8C) SHEET A.502, NOR LS101 OR LS102 SHOW THE LOCATION |
| | OF THE ELEVATOR MACHINE ROOM MUST MEET THE REQUIREMENTS |
| | OF SECTION 3005.1-3005.6 IF APPLICABLE, 2020 |
| | FBC-BUILDING CODE. MACHINE ROOMS CAN NOT BE IN THE |
| | LOBBY/ VESTIBULE. |
| | |
| | 9) SHEET A601 WINDOW DETAILS DO NOT SHOW THE USE OF |
| | FLASHING IN ACCORDANCE TO SECTION 1405.4 OF THE: 2020 |
| | FBC-BUILDING CODE SECTION 1405.4. FLASHINGS SHALL BE |
| | INSTALLED AT THE PERIMETERS OF EXTERIOR DOORS & WINDOW |
| | ASSEMBLIES. WHEN SELF-ADHERED MEMBRANES ARE USED AS |
| | FLASHINGS IN WALL ASSEMBLIES, THOSE SELF-ADHERED |
| | FLASHINGS SHALL COMPLY WITH AAMA-711. |
| | |
| | 10) SHEET M-102 HAS A NOTE FOR THE A/C STAND FOR |
| | CONDENSERS NOA 17-1226.24. PLEASE NOTE THIS NOA HAS |
| | BEEN SUPERSEDED BY NOA18-0828.09. |
| | |
| | 10A) ROOF TOP A/C STANDS MUST ALSO MEET THE MINIMUM |
| | HEIGHT REQUIREMENTS FOUND IN TABLE 1510.10 OF THE 2020 |
| | FBC-BUILDING CODE. HEIGHT OF THE STAND SHOULD BE |
| | MEASURED TO THE BOTTOM OF THE LOWEST HORIZONTAL FRAMING |
| | MEMBER OF THE STAND AND THE HEIGHT OF THE STAND DEPENDS |
| | ON THE WIDTH OF THE MECHANICAL UNIT. |
| | |
| | 10B) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| | FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| | OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| | THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| | WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| | ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| | STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| | IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| | |
| | 10C) FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C |
| | STANDS, AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF |
| | FRAMING & DECK AS WELL AS FROM THE CURB OR ROOF STAND |
| | TO THE EQUIPMENT ABOVE. |
| | |
| | 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 11) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |