Plan Review Notes
Plan Review Notes For Permit 22120560
Permit Number 22120560
Review Stop Z
Sequence Number 3
Notes
Date Text
2023-03-03 16:15:32FAILED
  
 1) UPDATED REPEAT COMMENT: BASED ON THE DECEMBER 29,
 2022 EMAIL FROM RICHARD GATHRIGHT, ASSISTANT BUILDING
 OFFICIAL, THE SCREEN FENCE IS PERMITTED TO BE INCLUDED
 WITH THE GENERATOR PERMIT, PROVIDED THAT THE FENCE
 INFORMATION IS INCLUDED WITH THE GENERATOR PERMIT. THIS
 ALSO INCLUDES ADJUSTING THE JOB VALUE TO INCLUDE THE
 COST TO INSTALL THE SCREEN FENCE. THE PERMIT FEE WAS
 NOT UPDATED TO REFLECT THE FENCE VALUE WITH THE PERMIT
 WAS RESUBMITTED. THE FEE ADJUSTMENT MUST BE SHOWN ON
 THE PERMIT PRIOR TO ZONING APPROVAL. **** THE RESPONSE
 LETTER STATES THAT THE VALUE OF THE FENCE WAS INCLUDED
 IN PERMIT 20121374, THE PERMIT FOR THE SITE FENCE.
 HOWEVER, THERE IS NO REFERENCE TO THE GENERATOR SCREEN
 WALL ON PERMIT 20121374, NOR WERE THE DETAILS OF THE
 GENERATOR SCREEN WALL INCLUDED WITH PERMIT NUMBER
 20101374. ADDITIONALLY, GENERATOR AND DUMPSTER
 ENCLOSURE WALLS ARE NOT REVIEWED AS PART OF A PERIMETER
 SITE FENCE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  