| Plan Review Notes For Permit 22120560 |
| Permit Number |
22120560 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-27 17:13:21 | FAILED | | | | | | 1) PROVIDE A SITE PLAN OR SURVEY SHOWING THE SETBACK TO | | | THE GENERATOR ENCLOSURE FENCE FROM THE PROPERTY LINE. | | | SINCE THE GENERATOR SCREEN FENCE SHOWN ON THE APPROVED | | | SITE PLAN IS 8 FEET IN HEIGHT, THE SETBACK MUST BE AT | | | LEAST 25 FEET. | | | | | | 2) PROVIDE THE SPECIFICATIONS SHEET FOR THE GENERATOR | | | THAT INCLUDES THE FULL HEIGHT OF THE GENERATOR, | | | INCLUDING THE MOUNTING PAD. | | | | | | 3) PROVIDE INFORMATION ON THE GENERATOR SCREEN FENCE TO | | | VERIFY THAT THE FULL HEIGHT OF THE GENERATOR WILL BE | | | SCREENED. THE SCREEN FENCE REQUIRES A SEPARATE PEMIT, | | | WITH PLANS, AND MUST BE INSTALLED PRIOR TO THE FINAL | | | INSPECTION FOR THE GENERATOR. | | | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | | [email protected] |
|