| 2023-01-12 18:10:16 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22120553 |
| | 255 EVERNIA ST # 204 |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | (1)-FLOORING SOUND INSULATION MATERIAL: |
| | (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION |
| | (2020). |
| | |
| | (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| | SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| | |
| | NOTE: |
| | SOUND INSULATION TEST SUBMITTED IS FOR A CONCRETE SLAB |
| | WITH A SUSPENDED ACOUSTICAL CEILING. THIS TEST DOESN'T |
| | MATCH BUILDING ACTUAL CONDITIONS. THERE IS NO |
| | ACOUSTICAL CEILING IN THIS BUILDING. NEED TO PROVIDE |
| | COPY OF TEST FOR CONCRETE SLAB WITHOUT ACOUSTICAL |
| | CEILING. |
| | |
| | (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| | SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| | |
| | NOTE: |
| | SOUND INSULATION TEST SUBMITTED IS FOR A CONCRETE SLAB |
| | WITH A SUSPENDED ACOUSTICAL CEILING. THIS TEST DOESN'T |
| | MATCH BUILDING ACTUAL CONDITIONS. THERE IS NO |
| | ACOUSTICAL CEILING IN THIS BUILDING. NEED TO PROVIDE |
| | COPY OF TEST FOR CONCRETE SLAB WITHOUT ACOUSTICAL |
| | CEILING. |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING |
| | CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE |
| | TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| | ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED |
| | ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| | |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | (2)PROVIDE FLOOR PLAN OR SKETCH OF APARTMENT SHOWING |
| | AREAS OF WORK. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |