| 2023-01-25 09:56:06 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.3.5.1.3 - SUBMIT A DIAGRAM THAT |
| | SHOWS THE MANIFOLDED LAYOUT OF THE WATERHEATERS WITH A |
| | WATER PIPING DIAGRAM. THE WATER PIPING DIAGRAM SHOULD |
| | INCLUDE WATER PIPE SIZES. I BELIEVE THIS IS PAGE P-8.3 |
| | FROM THE MASTER PLANS. INCLUDE THE WATER HEATER |
| | SCHEDULE AS WELL. |
| | |
| | 2. 2020 FPC 607.1.1 - IN THE DIAGRAM OF THE MANIFOLDED |
| | WATER HEATERS AND THE WATER PIPING DRAWING, INCLUDE A |
| | THERMOSTATIC MIXING VALVE AS REQUIRED BY THIS SECTION. |
| | |
| | 3. 2020 FPC 607.2.2 - THE RETURN LINE SHALL CONNECT TO |
| | THE COLD WATER INLET PIPE OF THE WATER HEATER AND THE |
| | COLD WATER INLET PIPE OR THE HOT WATER RETURN |
| | CONNECTION OF THE THERMOSTATIC MIXING VALVE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |