| 2023-01-25 10:09:41 | 1ST GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.3.5.1.5 - GAS - SUBMIT THE GAS |
| | DIAGRAM FOR THE WATER HEATER MANIFOLDING. INCLUDE PIPE |
| | SIZES FOR THE MANIFOLD. |
| | |
| | 2. 2020 FGC 503.2.3 - SHOW THE INTENDED EXHAUST VENTING |
| | IN A DIAGRAM THAT INCLUDES THE PIPE SIZES OF THE VENT |
| | PIPES FOR THE WATER HEATERS. IF YOU ARE GOING TO |
| | MANIFOLD THE EXHAUSTS, INCLUDE THE MANUFACTURERS' |
| | INSTRUCTIONS AND GUIDELINES THAT DETAIL THE EXHAUST |
| | MANIFOLD. |
| | |
| | 3. 2020 FGC 503.8 - SHOW THE TERMINATION OF THE VENT |
| | PIPING OF THE WATER HEATERS TO BE IN COMPLIANCE WITH |
| | THIS SECTION. SHOW THE REQUIRED SEPARATION DISTANCES |
| | BETWEEN THE EXHAUST TERMINATIONS FROM THE DIRECT VENT |
| | APPLIANCES AND OPENINGS INTO THE STRUCTURE, MECHANICAL |
| | INTAKES, ETC. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |