Plan Review Notes
Plan Review Notes For Permit 22120498
Permit Number 22120498
Review Stop G
Sequence Number 1
Notes
Date Text
2023-01-25 10:09:411ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.5 - GAS - SUBMIT THE GAS
 DIAGRAM FOR THE WATER HEATER MANIFOLDING. INCLUDE PIPE
 SIZES FOR THE MANIFOLD.
  
 2. 2020 FGC 503.2.3 - SHOW THE INTENDED EXHAUST VENTING
 IN A DIAGRAM THAT INCLUDES THE PIPE SIZES OF THE VENT
 PIPES FOR THE WATER HEATERS. IF YOU ARE GOING TO
 MANIFOLD THE EXHAUSTS, INCLUDE THE MANUFACTURERS'
 INSTRUCTIONS AND GUIDELINES THAT DETAIL THE EXHAUST
 MANIFOLD.
  
 3. 2020 FGC 503.8 - SHOW THE TERMINATION OF THE VENT
 PIPING OF THE WATER HEATERS TO BE IN COMPLIANCE WITH
 THIS SECTION. SHOW THE REQUIRED SEPARATION DISTANCES
 BETWEEN THE EXHAUST TERMINATIONS FROM THE DIRECT VENT
 APPLIANCES AND OPENINGS INTO THE STRUCTURE, MECHANICAL
 INTAKES, ETC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  