| 2022-12-16 14:53:58 | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW |
| | |
| | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. |
| | NEC 215.2, 220, 408.30 |
| | |
| | 2. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON |
| | MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN |
| | ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315 |
| | |
| | 3. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER |
| | NEC 440.14 OR IRC E4101.5 |
| | DISCONNECTING MEANS IS REQUIRED TO BE LOCATED ???WITHIN |
| | SIGHT FROM AND READILY ACCESSIBLE??? FROM THE |
| | AIR-CONDITIONING EQUIPMENT. |
| | |
| | 4. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 |
| | THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION |
| | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS |
| | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING |
| | OCCUPANCIES |
| | |
| | 5. THE ONE-LINE DIAGRAM IS NOT SHOWING INFORMATION OF |
| | SERVICE EQUIPMENT DISCONNECT (SERVICE OVERCURRENT |
| | PROTECTION) AS PER NEC 230 |
| | |
| | 6. AT LEAST ONE 120-VOLT, 20-AMPERE BRANCH CIRCUIT |
| | SHALL BE INSTALLED TO SUPPLY RECEPTACLE OUTLETS IN |
| | ATTACHED GARAGES AND IN DETACHED GARAGES WITH ELECTRIC |
| | POWER. THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS AS PER |
| | NEC 210.11(C)(4) |
| | |
| | 7. AT LEAST ONE 120-VOLT, 20-AMPERE BRANCH CIRCUIT |
| | SHALL BE PROVIDED TO SUPPLY THE BATHROOM(S) RECEPTACLE |
| | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS AS |
| | PER NEC 210.11(C)(3) |
| | |
| | END OF COMMENTS |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |