Plan Review Notes
Plan Review Notes For Permit 22120478
Permit Number 22120478
Review Stop E
Sequence Number 1
Notes
Date Text
2022-12-16 14:53:58FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE.
 NEC 215.2, 220, 408.30
  
 2. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON
 MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315
  
 3. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER
 NEC 440.14 OR IRC E4101.5
 DISCONNECTING MEANS IS REQUIRED TO BE LOCATED ???WITHIN
 SIGHT FROM AND READILY ACCESSIBLE??? FROM THE
 AIR-CONDITIONING EQUIPMENT.
  
 4. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11
 THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION
 FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS
 APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING
 OCCUPANCIES
  
 5. THE ONE-LINE DIAGRAM IS NOT SHOWING INFORMATION OF
 SERVICE EQUIPMENT DISCONNECT (SERVICE OVERCURRENT
 PROTECTION) AS PER NEC 230
  
 6. AT LEAST ONE 120-VOLT, 20-AMPERE BRANCH CIRCUIT
 SHALL BE INSTALLED TO SUPPLY RECEPTACLE OUTLETS IN
 ATTACHED GARAGES AND IN DETACHED GARAGES WITH ELECTRIC
 POWER. THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS AS PER
 NEC 210.11(C)(4)
  
 7. AT LEAST ONE 120-VOLT, 20-AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY THE BATHROOM(S) RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS AS
 PER NEC 210.11(C)(3)
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  