| 2023-03-07 12:47:05 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) ATTIC ACCESS ON THE DRAWINGS IS SHOWN AS 24X24 - |
| | PLEASE SHOW THE ATTIC ACCESS SIZE PER - FBC R807.1 THE |
| | ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN 22 INCHES |
| | BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE LOCATED IN |
| | A HALLWAY OR OTHER LOCATION WITH READY ACCESS. |
| | |
| | 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| | APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB |
| | 107.3.4 |
| | |
| | 3) PLEASE SHOW THE GENERATOR EXHAUST LOCATION TO BE 10 |
| | FEET FROM BUILDING OPENINGS - FBC R303.5.1 INTAKE |
| | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE |
| | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 |
| | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT |
| | |
| | 4) THE PROVIDED APPROVED LIST OF PRODUCT APPROVALS FROM |
| | THE ARCHITECT IS MISSING SOME OF THE PRODUCT APPROVALS |
| | THAT ARE UPLOADED TO PROJECTDOX AND SOME OF THE PRODUCT |
| | APPROVALS IN PROJECTDOX ARE NOT LISTED ON THE PRODUCT |
| | APPROVAL LIST FROM THE ARCHITECT. THE LISTED PRODUCT |
| | APPROVALS SHOULD MATCH THE PRODUCT APPROVALS LOADED |
| | INTO PROJECTDOX. PLEASE REVIEW THE LIST AND THE PRODUCT |
| | APPROVALS UPLOADED TO PROJECTDOX. IF NEEDED PLEASE E |
| | MAIL THE PERMIT LIBRARIAN TO REMOVE PRODUCT APPROVALS |
| | NOT NEEDED OR NOT LISTED ON THE APPROVED LIST FROM THE |
| | ARCHITECT. |
| | |
| | |
| | |
| | |