| 2022-12-16 14:50:53 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22120421 |
| | 12/16/22 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: SHOW THE DIAMETER OF THE SUPPLY PIPE FROM |
| | THE METER TO THE FIRST TEE. BASED ON THE 888,000 BTU |
| | LOAD SHOWN, A 1-INCH DIAMETER SCHEDULE 40 PIPE IS |
| | REQUIRED- TABLE 402.4(5) FBC FG. |
| | |
| | 2) GAS RISER: SHOW THE DIAMETER OF THE SCHEDULE 40 PIPE |
| | FROM THE 2LB. REG. TO THE TEE FOR THE INTERIOR RUN. |
| | BASED ON TABLE 402.4(3) A 3/4-INCH PIPE IS REQUIRED. |
| | |
| | 3) SURVEY: IT APPEARS THE TANKLESS WATER HEATER IS |
| | WITHIN 4 FT. OF THE BATHROOM WINDOW. PLEASE VERIFY THE |
| | WINDOW IS NON-OPERABLE OR RELOCATE THE UNIT- SEC. |
| | G2427.8 FBC RES. |
| | |
| | 4) SURVEY: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED |
| | TO THE RANGE AND PROVIDE CALCULATIONS- SEC. G2407.1 FBC |
| | RES. |
| | |
| | 5) GAS RISER AND SURVEY: A SEPARATE PERMIT IS REQUIRED |
| | FOR THE POOL HEATER. PLEASE LABEL IT AS FUTURE ON THE |
| | PLANS AND PROVIDE A GAS-TIGHT CAP- SEC. 105.1 WPB, AND |
| | SEC. G2415.15 FBC RES. |
| | |
| | 5) THE SIGNATURE OF THE CONTRACTOR OR QUALIFIER SHALL |
| | BE ON THE GAS RISER AND THE MARKED UP SURVEY- SEC. |
| | 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |