2022-12-28 11:14:57FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. DWELLING UNIT BATHROOMS SHAL BE IN ACCORDANCE WITH
 NEC 210.11(C)(3).
  
 2. CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION (PANEL
 SCHEDULE) NEEDS TO MATCH WITH LOAD CALCULATION, NEC
 408.4.
  
 3. MINIMUM WIRE SIZE FUSE OR CIRCUIT BREAKER SIZE PER
 TABLE NEC 240-3.
  
 4. PROVIDE A NOTE ON THE DRAWING FOR UNDERGROUND
 SERVICE, LATERALS SHALL HAVE THEIR LOCATION IDENTIFIED
 BY A
 WARNING RIBBON THAT IS PLACED IN THE TRENCH AT LEAST 12
 INCHES ABOVE THE UNDERGROUND INSTALLATION AS
 PER NEC 300-5 UNDERGROUND SERVICEPER.
  
 5. PROVIDE A NOTE ON THE DRAWING FOR ELECTRICAL PANEL
 AND ELECTRIC METER INSTALLATION AS PER NEC 110.14(D)
 CONDUCTOR TERMINATION, TORQUE - WHERE TIGHTENING TORQUE
 VALUES ARE INDICATED ON EQUIPMENT OR INSTALLATION
 INSTRUCTIONS, A CALIBRATED TORQUE TOOL MUST BE USED TO
 ACHIEVE THE INDICATED TORQUE VALUE, UNLESS THE
 EQUIPMENT
 MANUFACTURER PROVIDES AN ALTERNATIVE METHOD OF
 ACHIEVING THE REQUIRED TORQUE.
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  