| 2022-12-28 11:14:57 | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW |
| | |
| | 1. DWELLING UNIT BATHROOMS SHAL BE IN ACCORDANCE WITH |
| | NEC 210.11(C)(3). |
| | |
| | 2. CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION (PANEL |
| | SCHEDULE) NEEDS TO MATCH WITH LOAD CALCULATION, NEC |
| | 408.4. |
| | |
| | 3. MINIMUM WIRE SIZE FUSE OR CIRCUIT BREAKER SIZE PER |
| | TABLE NEC 240-3. |
| | |
| | 4. PROVIDE A NOTE ON THE DRAWING FOR UNDERGROUND |
| | SERVICE, LATERALS SHALL HAVE THEIR LOCATION IDENTIFIED |
| | BY A |
| | WARNING RIBBON THAT IS PLACED IN THE TRENCH AT LEAST 12 |
| | INCHES ABOVE THE UNDERGROUND INSTALLATION AS |
| | PER NEC 300-5 UNDERGROUND SERVICEPER. |
| | |
| | 5. PROVIDE A NOTE ON THE DRAWING FOR ELECTRICAL PANEL |
| | AND ELECTRIC METER INSTALLATION AS PER NEC 110.14(D) |
| | CONDUCTOR TERMINATION, TORQUE - WHERE TIGHTENING TORQUE |
| | VALUES ARE INDICATED ON EQUIPMENT OR INSTALLATION |
| | INSTRUCTIONS, A CALIBRATED TORQUE TOOL MUST BE USED TO |
| | ACHIEVE THE INDICATED TORQUE VALUE, UNLESS THE |
| | EQUIPMENT |
| | MANUFACTURER PROVIDES AN ALTERNATIVE METHOD OF |
| | ACHIEVING THE REQUIRED TORQUE. |
| | |
| | END OF COMMENTS |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |