2023-01-05 08:27:17CANNOT APPROVE THIS PERMIT UNTIL THE GENERATOR PERMIT-
 22020098 HAS BEEN APPROVED.
  
 1) PROVIDE THE MUFFLER DETAILS INCLUDING THE MAX.
 DISTANCE OF THE EXHAUST PIPING AND PIPING SIZES. FBC
 107.3.5
  
 2) PROVIDE A SITE PLAN INDICATING THE DISTANCE FROM
 GENERATOR EXHAUST TERMINATION LOCATION TO THE PROPERTY
 LINE. FMC 501.3.1
  
 3) IN DOING THE FUEL PORT AND PIPING REVIEW FOR THIS
 PROJECT I SEE THAT A REVISED SHEET M2.02G WAS SUBMITTED
 TO SHOW THE FUEL PIPING AND FUEL PORT. THERE IS A
 REVISION 10 ON THIS DRAWING THAT SHOWS A GEF-A AND
 GEF-B. I DO NOT SEE THESE ON THE APPROVED MASTER PERMIT
 APPROVED PLANS. PLEASE SUBMIT THE REVISION FOR THE
 ADDITION OF THESE EXHAUST FANS AND EXPLAIN THE REASON
 THEY WERE ADDED IN THIS REVISION. FBC 107.3.5
  
  