| Plan Review Notes For Permit 22120375 |
| Permit Number |
22120375 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-01-05 08:27:17 | CANNOT APPROVE THIS PERMIT UNTIL THE GENERATOR PERMIT- | | | 22020098 HAS BEEN APPROVED. | | | | | | 1) PROVIDE THE MUFFLER DETAILS INCLUDING THE MAX. | | | DISTANCE OF THE EXHAUST PIPING AND PIPING SIZES. FBC | | | 107.3.5 | | | | | | 2) PROVIDE A SITE PLAN INDICATING THE DISTANCE FROM | | | GENERATOR EXHAUST TERMINATION LOCATION TO THE PROPERTY | | | LINE. FMC 501.3.1 | | | | | | 3) IN DOING THE FUEL PORT AND PIPING REVIEW FOR THIS | | | PROJECT I SEE THAT A REVISED SHEET M2.02G WAS SUBMITTED | | | TO SHOW THE FUEL PIPING AND FUEL PORT. THERE IS A | | | REVISION 10 ON THIS DRAWING THAT SHOWS A GEF-A AND | | | GEF-B. I DO NOT SEE THESE ON THE APPROVED MASTER PERMIT | | | APPROVED PLANS. PLEASE SUBMIT THE REVISION FOR THE | | | ADDITION OF THESE EXHAUST FANS AND EXPLAIN THE REASON | | | THEY WERE ADDED IN THIS REVISION. FBC 107.3.5 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|