| 2022-12-20 12:44:51 | 1ST REVIEW FMC | | | PERMIT: 22120375 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE VALUE GIVEN ON THE PERMIT APPLICATION APPEARS TO | | | BELOW FOR THIS PROJECT. PROVIDE THE CORRECTED VALUE FOR | | | THIS PROJECT. | | | | | | 2) PROVIDE THE MUFFLER DETAILS INCLUDING THE MAX. | | | DISTANCE OF THE EXHAUST PIPING AND PIPING SIZES. FBC | | | 107.3.5 | | | | | | 3) PROVIDE A SITE PLAN INDICATION THE DISTANCE FROM | | | GENERATOR EXHAUST TERMINATION LOCATION TO THE PROPERTY | | | LINE. FMC 501.3.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|