| 2022-12-16 16:07:53 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22120353 |
| | 12/16/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | FDHA- FAIR HOUSING DESIGN ACT MANUAL |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE EDGE CONDOMINIUMS WERE DESIGNED IN ACCORDANCE |
| | WITH THE FAIR HOUSING ACT, WHICH REQUIRES ALTERATIONS |
| | IN THE DWELLINGS TO ALSO BE IN COMPLIANCE. BASED ON THE |
| | FLOOR PLAN DRAWINGS SHOWING THE TOILETS ADJACENT TO THE |
| | BATHTUBS IT APPEARS TYPE A COMPLIANCE WAS THE DESIGN |
| | INTENTION FOR THE UNIT. TYPE A DESIGN ALLOWS FOR A |
| | 30X48 INCH CLEAR FLOOR SPACE FORWARD APPROACH TO THE |
| | TUB HOWEVER SHOWERS REQUIRE A 30X40 INCH CLEAR FLOOR |
| | SPACE POSITIONED PARALLEL APPROACH TO THE SHOWER. IT |
| | APPEARS THE CLEAR FLOOR SPACE CANNOT BE PROVIDED UNLESS |
| | THE TOILET IS RELOCATED. PLEASE SEE PAGES 7.34-7.38, |
| | AND 7.56-7.58 OF THE FHDA MANUAL FOR FURTHER |
| | INFORMATION AND PROVIDE AN ENLARGED DRAWINGS IN |
| | COMPLIANCE WITH COMMENTS 2 & 3 LISTED BELOW. |
| | |
| | PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE |
| | GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND |
| | DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE |
| | A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE |
| | ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET |
| | THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY |
| | GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO |
| | REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF |
| | REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN, |
| | PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A |
| | COPY OF THE FAIR HOUSING AFFIDAVIT. |
| | |
| | 2) PLEASE REFER TO PAGES 7.56- 7.59 OF THE FHDA MANUAL |
| | AND INDICATE ON THE PLANS THE REQUIRED 30X48-INCH CLEAR |
| | FLOOR SPACES POSITONED FOR PARALLEL APPROACHES TO THE |
| | SHOWER. PLEASE NOTE THAT NO FIXTURES ARE ALLOWED TO |
| | OVERLAP THE CLEAR FLOOR SPACES REQUIRED FOR THE SHOWER. |
| | |
| | 3) REFER TO PAGES 6.12- 6.13 OF THE FHDA MANUAL AND |
| | PROVIDE AN ELEVATION DETAIL SHOWING THE SHOWER CONTROLS |
| | LOCATION, AND THE GRAB BAR AND SEAT REINFORCEMENT |
| | DETAILS. SHOW THE LENGTHS, WIDTHS AND HEIGHTS AND THE |
| | TYPE OF REINFORCEMENT MATERIAL TO BE USED. SEE SECTION |
| | 603.1 FOR ALLOWABLE MATERIALS IN NON-COMBUSTIBLE |
| | BUILDINGS. |
| | |
| | 4) THE SIGNATURE OF THE CONTRACTOR OR QUALIFIER SHOW BE |
| | ON THE DRAWINGS- SEC.107.2.1 WPB, AND FL. STATUTES |
| | 471.003(2)(H) & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |