| Plan Review Notes For Permit 22120298 |
| Permit Number |
22120298 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-13 10:29:37 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | PROVIDE THE FOLLOWING INFORMATION FOR FLOORING | | | SUBMITTALS: | | | | | | 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK. | | | DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC AMENDMENTS | | | 107.2.1. | | | 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING. | | | 3. TYPE OF PROPOSED (HARD) FINISH FLOOR COVERING (TILE, | | | LAMINATE, WOOD, MARBLE, ETC.). | | | 4. FBC 603.1 FLAME SPREAD - ASTM E 84-09 | | | | | | FBC 2603 FOAM PLASTIC INSULATION | | | 2603.3 SURFACE-BURNING CHARACTERISTICS. | | | UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM | | | PLASTIC INSULATION AND FOAM PLASTIC CORES OF | | | MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX | | | OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT | | | MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS | | | INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL | | | 723. LOOSE FILL-TYPE FOAM PLASTIC INSULATION SHALL BE | | | TESTED AS BOARD STOCK FOR THE FLAME SPREAD AND | | | SMOKE-DEVELOPED INDEXES. | | | | | | | | | |
|