2023-04-21 12:02:312ND REVIEW FBC-2020 PLUMBING
 PERMIT-22120277
 4/21/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P.106A, P.106B, P.106C, P.106D, P.107A,
 P.107B, P.107C, P.107D, P.108A, P.108C SHOW SIDEWALL
 ROOF DRAINS AND IN SOME CASES DRAIN PIPES PENETRATING
 STAIRWAY WALLS. PLEASE REFER TO SEC. 1023.5 FBC B. AND
 NOTE PENETRATIONS INTO FIRE-RATED INTERIOR EXIT
 STAIRWAYS ARE PROHIBITED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  