| 2023-05-01 07:41:27 | 1ST REVIEW FMC |
| | PERMIT: 22120277 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M.208B: ADD A NOTE TO THE MECHANICAL DRAWINGS |
| | STATING THAT THE KITCHEN HOODS AND ALL DUCTS ASSOCIATED |
| | WILL REQUIRE A SEPARATE PERMIT APPLICATION INCLUDING |
| | SUBMITTAL AND A SEPARATE REVIEW AS IT WILL NOT BE |
| | REVIEWED UNDER THIS PERMIT. |
| | 2) I DO NOT SEE THE EF THAT IS EXHAUSTING THE NEW MENS |
| | AND WOMENS RESTROOMS SHOWN ON SHEET M.208C. PLEASE |
| | INCLUDE IT ON SHEET M.602. FBC 107.3.5 |
| | 3) PLEASE SHOW EF-52 AND EF-55 ON SHEET M.602 AS WELL. |
| | FBC 107.3.5 |
| | 4) SHEET M.606: OUTDOOR AIR FOR AHU-10A AND 10B ??? |
| | TENNIS COURT SPORT AND AMUSEMENT / ARENA- PLAY AREA: |
| | THE OUTDOOR AIR SHOULD BE CALCULATED WITH AN OCCUPANT |
| | DENSITY OF 7 ALSO WITH PEOPLE OUTDOOR AIR RATE OF 20 |
| | CFM. THE AREA OUTDOOR AIRFLOW RATE SHOULD BE CALCULATED |
| | WITH .18 CFM PER SQ.FT. THIS WOULD GIVE YOU 94 PEOPLE X |
| | 20 = 1880; THE AREA OUTDOOR AIRFLOW RATE WOULD BE- |
| | 13404 X .18 = 2413; 1880 + 2413 = 4293 CFMS OF REQUIRED |
| | OUTDOOR AIR FOR THE SPACE. WE ARE CURRENTLY IN THE 2020 |
| | 7TH EDITION OF THE FLORIDA MECHANICAL CODE. PLEASE |
| | CORRECT THE NAME OF THE OUTDOOR AIR SHEET. FMC TABLE |
| | 403.3.1.1 |
| | 5) PROVIDE AN EQUIPMENT LIST FOR THE NEW LEVEL 08 EVENT |
| | KITCHEN. FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |