| 2023-01-10 06:40:07 | 1ST REVIEW FMC |
| | PERMIT: 22120277 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE FOLLOWING SHEETS WERE NOT SUBMITTED BUT ARE |
| | LISTED AS PART OF THIS REVISION. PLEASE PROVIDE THESE |
| | DRAWINGS FOR REVIEW. M.208A; M.208B; M.209; M.602; |
| | M.603; M.604. FBC 107.3.5 |
| | |
| | 2) SHEET M.208C; PLEASE IDENTIFY THE NEW VESTIBULE 0843 |
| | AND THE NEW ADDED SUPPLY DUCT. FBC 107.3.5 |
| | |
| | 3) SHEET M.208D: THE SCHEDULE SHEETS WERE NOT SUBMITTED |
| | FOR ME TO CHECK AC 7B CFM TO SEE IF A SMOKE DETECTOR IS |
| | REQUIRED, PLEASE VERIFY IF IT IS OR NOT. FMC 606 |
| | |
| | 4) PROVIDE THE REVIEWER WITH A RISER DRAWING FOR THE |
| | CHANGES TO M.209, M.210, M.211. FBC 107.3.5 |
| | |
| | 5) SHEET M.227: THE NEW AIR BALANCE CHART SHOULD ALSO |
| | BE INCLUDED ON THE HOOD DETAIL SHEET FOR THE BANQUET |
| | KITCHEN. PLEASE MAKE THE CHANGE AND SUBMIT THAT DRAWING |
| | AS WELL. FBC 107.3.5 |
| | |
| | 6) SHEET M.227: PLEASE PROVIDE THE OUTDOOR AIR |
| | CALCULATIONS FOR THE AREAS LISTED IN THE NEWLY ADDED |
| | AIR BALANCE REPORT. FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |