Plan Review Notes
Plan Review Notes For Permit 22120266
Permit Number 22120266
Review Stop E
Sequence Number 2
Notes
Date Text
2023-05-10 13:27:54ELECTRIC REVIEW FAILED
  
 1) OVERCURRENT PROTECTION IN ELECTRIC PANEL A FOR
 ELECTRIC PANEL B IS DETAILED AS 100 AMP. RISER DIAGRAM
 DETAILS ELECTRIC PANEL B AS 200 AMP. IT IS THE
 EXPERIENCE OF THIS REVIEWER THAT A 200 AMP BREAKER IS
 OVER THE MAXIMUM ALLOWED BY ELECTRIC PANEL MANUFACTURES
 AND THE ONLY CONFIGURATION I AM AWARE OF IS A 200 AMP
 FEED THROUGH PANEL FEEDING A 200 AMP SUB PANEL.
 UTILIZING AN ENGINEER OR QUALIFIED ELECTRICAL
 CONTRACTOR FAMILIAR WITH PREPARING RISER DIAGRAMS IS
 RECOMMENDED TO PREPARE A RISER DIAGRAM THAT WILL COMPLY
 WITH NEC CODES AND MANUFACTURER SPECIFICATIONS. NEC
 215.5
  
 2) PANEL SCHEDULES DETAIL 2 AIR HANDLERS WITH 60 AMP
 OVERCURRENT PROTECTION. IT IS THE EXPERIENCE OF THIS
 REVIEWER THAT AIR HANDLERS WITH THIS SIZE OCP CONTAIN A
 10KW HEAT STRIP NOT A 7.5 AS DETAILED IN LOAD
 CALCULATIONS SUBMITTED. PLEASE PROVIDE THE
 SPECIFICATIONS FOR BOTH AIR HANDLERS AND DETAIL THE
 CORRECT SIZE OCP AS APPLICABLE
  
 3) PANEL SCHEDULES DETAIL 2 TANKLESS WATER HEATERS WITH
 40 AMP OVERCURRENT AND 50 AMP OCP PROTECTION. THE PANEL
 SCHEDULES SUGGEST A KW RATING OF THESE WATER HEATERS AS
 9600 AND 12000 KW. THE LOAD CALCULATION DETAILS THESE
 WATER HEATERS AS HAVING A 24,000 KW AND 18,000 KW
 RATING AS DETAILED IN LOAD CALCULATIONS SUBMITTED.
 PLEASE PROVIDE THE SPECIFICATIONS FOR BOTH TANKLESS
 WATER HEATERS AND DETAIL THE CORRECT SIZE OCP AS
 APPLICABLE.
  
 4) BOTH ELECTRIC PANELS ARE STILL DETAILED IN CLOSETS
 AND NOT IN COMPLIANCE WITH NEC 240.24 (D) PLEASE
 RELOCATE TO A CODE COMPLIANT LOCATION
 .
 5) LOAD CALCULATION PROVIDED IN SUBMITTAL IS STILL
 INCORRECT. LOADS LISTED APPEAR TO BE INCORRECT, SEE
 ABOVE, AND DEMAND FACTORS ARE STILL BEING USED FOR SUB
 PANEL B LOAD IN ELECTRIC PANEL A CALCULATION. PLEASE
 SUBMIT A CALCULATION IN COMPLIANCE WITH EITHER NEC
 220.40, STANDARD CALCULATION, OR NEC 220.80 OPTIONAL
 CALCULATION. AS STATED ABOVE UTILIZING AN ENGINEER OR
 QUALIFIED ELECTRICAL CONTRACTOR FAMILIAR WITH THESE
 CALCULATIONS IS RECOMMENDED.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  