| 2023-03-03 15:50:23 | ELECTRIC REVIEW FAILED |
| | |
| | 1) PROVIDE A CORRECT ELECTRIC LOAD CALCULATION FOR |
| | PANEL A. THE ELECTRIC LOAD CALCULATION SUBMITTED |
| | INCORRECTLY LISTS THE, CALCULATED DEMAND LOAD, FROM |
| | PANEL B INSTEAD OF THE ACTUAL ELECTRIC LOADS. THE |
| | CORRECT CALCULATION WILL CALCULATE ALL LOADS FOR THE |
| | MAIN SERVICE FEEDERS FROM THE METER TO PANEL A, |
| | ACCORDING TO NEC 220.40, STANDARD CALCULATION OR |
| | 220.80, OPTIONAL CALCULATION |
| | |
| | 2) PLEASE INDICATE ON ELECTRICAL FLOOR PLAN THE |
| | REQUIRED ELECTRICAL EQUIPMENT WORKING DEPTH OF 3??? FOR |
| | ALL AIR CONDITIONING CONDENSER DISCONNECTS AS REQUIRED |
| | PER NEC 110.26 |
| | |
| | 3) PLEASE DETAIL THE REQUIRED OUTDOOR RECEPTACLES AT |
| | THE FRONT AND SIDE ENTRY OF THE HOUSE AS PER NEC |
| | 210.52(E)(3) BALCONIES, DECKS, AND PORCHES. BALCONIES, |
| | DECKS, AND PORCHES THAT ARE ATTACHED TO THE DWELLING |
| | UNIT AND ARE ACCESSIBLE FROM INSIDE THE DWELLING UNIT |
| | SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE |
| | FROM THE BALCONY, DECK, OR PORCH. |
| | |
| | 4) PLEASE NOTE PANEL B IS LOCATED IN A STORAGE ROOM. |
| | ELECTRICAL INSPECTORS MAY CONSIDER THIS ROOM AS NOT IN |
| | COMPLIANCE WITH NEC 240.24 (D) NOT IN VICINITY OF |
| | EASILY IGNITABLE MATERIAL. OVERCURRENT DEVICES SHALL |
| | NOT BE LOCATED IN THE VICINITY OF EASILY IGNITABLE |
| | MATERIAL, SUCH AS IN CLOTHES CLOSETS. A CHANGE OF |
| | LOCATION SHOULD BE CONSIDERED OR A NOTE STATING |
| | COMPLIANCE WITH THE ABOVE NEC CODE |
| | |
| | 5) PLEASE CHANGE THE ARC FAULT PROTECTION NOTE TO ONE |
| | STATING COMPLIANCE WITH THE 2017 NEC CODE 210.12 AS |
| | OUTLINED BELOW. ALL 120-VOLT, SINGLE PHASE, 15 AND 20 |
| | AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING |
| | UNIT KITCHENS, LAUNDRY ROOMS, FAMILY ROOMS, DINING |
| | ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| | PROTECTION. NEC 210.12; FBC RE3902.16 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |
| | |