Plan Review Notes
Plan Review Notes For Permit 22120266
Permit Number 22120266
Review Stop E
Sequence Number 1
Notes
Date Text
2023-03-03 15:50:23ELECTRIC REVIEW FAILED
  
 1) PROVIDE A CORRECT ELECTRIC LOAD CALCULATION FOR
 PANEL A. THE ELECTRIC LOAD CALCULATION SUBMITTED
 INCORRECTLY LISTS THE, CALCULATED DEMAND LOAD, FROM
 PANEL B INSTEAD OF THE ACTUAL ELECTRIC LOADS. THE
 CORRECT CALCULATION WILL CALCULATE ALL LOADS FOR THE
 MAIN SERVICE FEEDERS FROM THE METER TO PANEL A,
 ACCORDING TO NEC 220.40, STANDARD CALCULATION OR
 220.80, OPTIONAL CALCULATION
  
 2) PLEASE INDICATE ON ELECTRICAL FLOOR PLAN THE
 REQUIRED ELECTRICAL EQUIPMENT WORKING DEPTH OF 3??? FOR
 ALL AIR CONDITIONING CONDENSER DISCONNECTS AS REQUIRED
 PER NEC 110.26
  
 3) PLEASE DETAIL THE REQUIRED OUTDOOR RECEPTACLES AT
 THE FRONT AND SIDE ENTRY OF THE HOUSE AS PER NEC
 210.52(E)(3) BALCONIES, DECKS, AND PORCHES. BALCONIES,
 DECKS, AND PORCHES THAT ARE ATTACHED TO THE DWELLING
 UNIT AND ARE ACCESSIBLE FROM INSIDE THE DWELLING UNIT
 SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE
 FROM THE BALCONY, DECK, OR PORCH.
  
 4) PLEASE NOTE PANEL B IS LOCATED IN A STORAGE ROOM.
 ELECTRICAL INSPECTORS MAY CONSIDER THIS ROOM AS NOT IN
 COMPLIANCE WITH NEC 240.24 (D) NOT IN VICINITY OF
 EASILY IGNITABLE MATERIAL. OVERCURRENT DEVICES SHALL
 NOT BE LOCATED IN THE VICINITY OF EASILY IGNITABLE
 MATERIAL, SUCH AS IN CLOTHES CLOSETS. A CHANGE OF
 LOCATION SHOULD BE CONSIDERED OR A NOTE STATING
 COMPLIANCE WITH THE ABOVE NEC CODE
  
 5) PLEASE CHANGE THE ARC FAULT PROTECTION NOTE TO ONE
 STATING COMPLIANCE WITH THE 2017 NEC CODE 210.12 AS
 OUTLINED BELOW. ALL 120-VOLT, SINGLE PHASE, 15 AND 20
 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING
 UNIT KITCHENS, LAUNDRY ROOMS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION. NEC 210.12; FBC RE3902.16
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved