| Plan Review Notes For Permit 22120245 |
| Permit Number |
22120245 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-03 14:07:09 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) CITY OF WPB AMENDMENTS TO FBC B FIGURE 1609.3(1), | | | THE WINDLOADS THAT ARE INDICATED WITHIN THE ENGINEER'S | | | LETTER SHOW AN ULT DESIGN WIND SPEED OF 164 MPH. THIS | | | NEEDS TO BE CHANGED TO 170 MPH (ULT). | | | | | | 2.) NOTICE: THE PLAN SHEETS AND ENGINEERING LETTERS | | | NEED TO HAVE 3RD PARTY VERIFIABLE SIGNATURES BY DESIGN | | | PROFESSIONALS. | | | A. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A | | | VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND | | | SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A | | | VALID DIGITAL SIGNATURE. | | | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR | | | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH | | | 61G1-16 AND 61G15, F.A.C. | | | B. SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE. | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. | | | 481, F.S. & 61G1. | | | |
|