Plan Review Notes
Plan Review Notes For Permit 22120237
Permit Number 22120237
Review Stop B
Sequence Number 1
Notes
Date Text
2023-01-13 10:17:29WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22120237
 ADD: 777 S. FLAGLER DR. 18TH FLOOR NEEDS TENTANT SUITE
 NUMBER
 CONT: TURNER CONSTRUCTION
 TEL: 305-216-4341
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 13TH/ 2023
 ACTION: DENIED
  
 1A) THE COVERSHEET HAS A SITE MAP OF THE 18TH FLOOR,
 SCOPE OF WORK IS NOT THE WHOLE FLOOR, NEEDS TENANT
 SUITE NUMBER TO BE ASSIGNED!!!!! 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
 2020 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 1B) CODE INFORMATION STATES THE CONSTRUCTION TYPE AS IB
 PLEASE REVIEW IN THE 2020 FBC-B TABLE 504.4 A IB
 BUILDING BUSINESS OCCUPANCY CAN ONLY BE 12 STORIES. IA
 THE BUILDING HEIGHT IS UNLIMITED. SAME NOTE CHAPTER 4 &
 5 THE CONSTRUCTION TYPE IB PLEASE UPDATE. NOTE. CHAPTER
 6 CONSTRUCTION TYPE CORRECT IA.
  
 2) D118 DEMOLITION FLOOR PLAN NOTE # 5 PREPARE EXISTING
 REMAINING OPENINGS TO RECEIVE NEW BASE CABINETS. REFER
 TO ELEVATIONS AND DETAILS. SHEET A400 CAF?? NORTH
 ELEVATION EXISTING FAUCET AND BACKSPLASH TO REMAIN.
 EXISTING MILLWORK TO REMAIN (CABINETRY). PLEASE
 EXPLAIN, IF THE CABINETRY AND SINK ARE TO REMAIN THEN
 THEY MUST COMPLY WITH THE 2020 FBC-ACCESSIBILITY CODE
 SECTIONS:
  
 2A) 606 SINKS> 2020 FBC-ACCESSIBILITY CODE SECTION
 606.3 HEIGHT. SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2B) 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED
 CLEAR FLOOR SPACE ON THE FLOOR PLAN.
  
 2C) 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY &
 DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
  
 2D) 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  