Plan Review Notes
Plan Review Notes For Permit 22120224
Permit Number 22120224
Review Stop M
Sequence Number 2
Notes
Date Text
2023-02-27 09:48:07THIS NEW ADDITION WILL NEED TO MEET THE REQUIREMENTS OF
 THE ENERGY CODE. IF THE EXISTING MECHANICAL SYSTEM IS
 TO BE USED TO CONDITION THE NEW ADDITION A MECHANICAL
 EQUIPMENT SIZING CALCULATION SHALL BE PROVIDED. A
 MECHANICAL DRAWING SHALL BE PROVIDED SHOWING THE DUCT
 CONNECT, SIZE AND CFM'S TO THE NEW ADDITION.
 PROVIDE THE DOCUMENTATION REQUESTED IN THE 1ST CYCLE
 MECHANICAL REVIEW.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS ADDITION.
 FEC R101.5.1.1.1
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS EDITION. FEC R403.7.1
  
 3) PROVIDE MECHANICAL DRAWING FOR THE MECHANICAL DESIGN
 FOR THIS ADDITION. FBC 107.3.5
  
 4) SHOW THE BATHROOM EXHAUST FAN, DUCTWORK AND
 TERMINATION LOCATION. FRC R303.3
  