| 2023-07-26 14:29:32 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) THE PLANS HAVE BEEN REVISED TO SHOW A WOOD ROOF DECK |
| | - PRODUCT APPROVAL 17-0511.03 IS FOR A STEEL ROOF DECK |
| | - PLEASE REVISE THE ROOF SYSTEM PRODUCT APPROVAL. IN |
| | THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK - |
| | PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE |
| | ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON |
| | THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL |
| | SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT |
| | OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A |
| | HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT |
| | APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7 ON THE |
| | PRODUCT APPROVAL. |
| | |
| | 2) PLEASE PROVIDE A PRODUCT APPROVAL FOR THE TILE |
| | ROOFING - PLEASE CIRCLE THE ROOF TILE ATTACHMENT TYPE |
| | IN THE PRODUCT APPROVAL. ALL PRODUCT APPROVALS NEED TO |
| | BE REVIEWED AND MARKED APPROVED BY THE BUILDING |
| | DESIGNER OF RECORD FBC WPB 107.3.4 |
| | |
| | 3) THE EXTERIOR WALL CLADDING SYSTEM ON DRAWING A-5.00 |
| | IS DIFFERENT THEN THE STRUCTURAL DRAWINGS WHICH SHOW |
| | STRUCTURAL SHEATHING THE PRODUCT APPROVAL PROVIDED IS |
| | ALSO DIFFERENT - PLEASE SHOW ALL EXTERIOR WALL CLADDING |
| | COMPONETS SIZE, THICKNESS AND ATTACHMENTS - FBC WPB |
| | 107.2.1 |
| | |
| | 4) PLEASE SHOW THE EXTERIOR WALL WATER RESISTIVE |
| | BARRIER - FBC R703.2 WATER-RESISTIVE BARRIER. |
| | ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND |
| | BREAKS, COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR |
| | OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED |
| | OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS. |
| | |
| | 5) PRODUCT APPROVAL FOR THE EXTERIOR WALL CLADDING WILL |
| | NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING |
| | DESIGNER OF RECORD - FBC WPB 107.3.4 |
| | |
| | 6) PRODUCT APPROVAL FL20468 -R5 NEEDS TO BE REVIEWED |
| | AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD |
| | - FBC WPB 107.3.4 |
| | |
| | 7) PRODUCT APPROVAL FL23358-R5 NEEDS TO BE REVIEWED AND |
| | MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD - |
| | FBC WPB 107.3.4 |
| | |
| | 8) PRODUCT APPROVAL FL26095-R3 NEEDS TO BE REVIEWED AND |
| | MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD - |
| | FBC WPB 107.3.4 |
| | |
| | 9) PRODUCT APPROVAL NOA 19-0305.03 NEEDS TO BE REVIEWED |
| | AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD |
| | - FBC WPB 107.3.4 |
| | |
| | |
| | |
| | |
| | |
| | |