Plan Review Notes
Plan Review Notes For Permit 22120135
Permit Number 22120135
Review Stop E
Sequence Number 1
Notes
Date Text
2023-02-16 12:07:13FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW INFORMATION PROVIDED ON PAGE E601 SERVICE
 CONDUCTORS FROM THE ELECTRIC METER TO THE 2P-200A
 DISCONNECT (3#3/0 AWG THWN CU + 1#6 AWG THWN CU). NEC
 250.102
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  