| Notes |
| Date |
Text |
| 2022-12-16 11:51:36 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | | | 1. SUBMITTED PRODUCT APPROVAL FL18355-R6 HAS BEEN | | | REVISED TO FL18355-R8. PLEASE PROVIDE A COMPLETE SET. | | | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY | | | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS | | | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT | | | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER | | | RULE 61G20-3. | | | 2. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF | | | DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING | | | CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), | | | MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW | | | POSITIVE DRAINAGE. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|