| 2022-12-29 16:25:15 | 1ST BUILDING REVIEW |
| | RESULTS: CORRECTIONS NEEDED |
| | |
| | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| | PLANS EXAMINER II |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| | |
| | NOTICE: A SEPERATE PERMIT IS REQUIRED FOR THE GARAGE |
| | CONVERSION. (SOUTH BLDG) PLANS SHALL REMAIN UNDER |
| | 22120126 (MAIN DWELLING UNIT). PERMITS SALL TRAVEL |
| | TOGETHER. |
| | VALUE MAY BE PRO-RATED. |
| | |
| | 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE |
| | SURVEY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. PROVIDE A SITE PLAN.... |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE |
| | AND INCLUDED BOUNDARY LINE SURVEY. |
| | |
| | 3. PROVIDE AN ENERGY SUBMITTAL. RESIDENTIAL (RE) |
| | R401.2COMPLIANCE. |
| | SECTION R405 AND THE PROVISIONS OF SECTIONS R401 |
| | THROUGH R404 LABELED MANDATORY. |
| | |
| | 4.IDENTIFY THE CEILING AND WALL INSULATION TYPE AND |
| | R-VALUE ON PLANS. |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | 5.PROVIDE THE SOURCE OF REQUIRED HEATING PER R303.10 |
| | DESIGN TEMP. WEST PALM BEACH FLORIDA ??? 45 DEGREES - |
| | WINTER |
| | |
| | 6. NOT ENOUGH INFORMATION PROVIDED TO DETERMINE 1. |
| | LEVEL OF ALTERATION, 2. CONSTRUCTION TYPE AND 3. |
| | OCCUPANCY GROUP. |
| | PROVIDE A SECTION VIEW OF THE EXTERIOR WALLS. IDENTIFY |
| | TYPE OF CONSTRUCTION. |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | ARE ANY WINDOWS OR DOORS BEING REPLACED OR NEWLY |
| | INSTALLED? |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |