| Date |
Text |
| 2023-01-17 07:24:35 | 2ND GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. COMMENT NOT ADDRESSED. NEED THE BTU LOAD OF THE |
| | WATER HEATER AND RANGE. NEED A RISER DRAWING WITH PIPE |
| | SIZES AND MATERIALS USED. LIST THE PRESSURES ON THE |
| | DRAWING. INCLUDE YOUR TABLE FROM THE FUEL GAS CODE THAT |
| | YOU USED FOR SIZING. |
| | NOTE: YOU INDICATED ON THE CONTRACT THAT PVC WAS TO BE |
| | USED AND PVC CANNOT BE USED FOR GAS PIPING. |
| | 2020 FRC G2413.3 (402.3) - PLEASE INCLUDE A GAS RISER. |
| | INCLUDE PIPE SIZES, MATERIALS USED, BTU LOADS AND GAS |
| | PRESSURES INVOLVED. ALSO INCLUDE A REFERENCE FOR THE |
| | TABLE FROM THE GAS CODE THAT WAS USED FOR SIZING THE |
| | SYSTEM. |
| | |
| | 2. COMMENT NOT ADDRESSED. PLEASE MAKE SURE THE PERSON |
| | WHO DESIGNS THE DRAWING SIGNS IT, INCLUDING THE |
| | CONTRACTOR LICENSE NUMBER. |
| | 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO |
| | DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME, |
| | AS WELL AS PUT THE CONTRACTOR'S NUMBER ON THE DRAWING |
| | AS REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |