2023-06-13 13:11:11ELECTRIC REVIEW FAILED
  
 1) NO DESCRIPTION OF WORK CAN BE FOUND ON THE
 APPLICATION. OTHER DOCUMENTS STATE DEMO OF 2
 UNPERMITTED BATHROOMS. OTHER DOCUMENTS STATE A FLOOR
 PLAN WOULD BE SUBMITTED HOWEVER NONE WAS FOUND. PLEASE
 PROVIDE A FLOOR PLAN AND NARRITIVE DETAILING ALL WORK
 TO BE DONE. ALSO AS STATED IN PREVIOUSE REVIEW, WEST
 PALM BEACH PLAN REVIEW REQUIRES AN ELECTRICAL PERMIT
 APPLICATION FOR APPROVAL. THIS IS A BUILDING DEPARTMENT
 POLICY TO ENSURE ELECTRICAL SAFETY DURING DEMOLITION.
 FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  