Plan Review Notes
Plan Review Notes For Permit 22120004
Permit Number 22120004
Review Stop E
Sequence Number 1
Notes
Date Text
2022-12-27 10:41:45ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE FLOOR PLAN LOCATIONG ALL EQUIPMENT TO
 BE WIRED. FBC 107.2
 2) PLEASE PROVIDE ALL CONDUIT, CONDUCTOR , OVERCURRENT
 AND EQUIPMENTS SIZES AND SPECIFICATIONS. FBC 107.2
 3) PLEASE INDICATE WIRING METHODS USED FOR THIS
 INSTALLATION
 4) PLEASE PROVIDE LOAD CALCULATION AND PANEL SCHEDULE
 FOR PANEL UPSTREAM OF NEW EQUIPMENT.
 5) VALUE FOR WORK STATED ON PERMIT APPLICATION STATED
 AS $0. ELECTRIC WORK IS NOT INCLUDED IN AC CONTRACT.
 PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, OR, AT
 YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR PROVIDE A
 REASONABLE VALUE. WPB F.B.C. 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  