| Plan Review Notes For Permit 22120004 |
| Permit Number |
22120004 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-27 10:41:45 | ELECTRIC REVIEW FAILED | | | 1) PLEASE PROVIDE FLOOR PLAN LOCATIONG ALL EQUIPMENT TO | | | BE WIRED. FBC 107.2 | | | 2) PLEASE PROVIDE ALL CONDUIT, CONDUCTOR , OVERCURRENT | | | AND EQUIPMENTS SIZES AND SPECIFICATIONS. FBC 107.2 | | | 3) PLEASE INDICATE WIRING METHODS USED FOR THIS | | | INSTALLATION | | | 4) PLEASE PROVIDE LOAD CALCULATION AND PANEL SCHEDULE | | | FOR PANEL UPSTREAM OF NEW EQUIPMENT. | | | 5) VALUE FOR WORK STATED ON PERMIT APPLICATION STATED | | | AS $0. ELECTRIC WORK IS NOT INCLUDED IN AC CONTRACT. | | | PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, OR, AT | | | YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR PROVIDE A | | | REASONABLE VALUE. WPB F.B.C. 109.3 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | | | | |
|