| Plan Review Notes For Permit 22111281 |
| Permit Number |
22111281 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-31 11:51:02 | 1) APPROVED WITH PRIVISO: THE TRANSFER DUCT FOR THE | | | BEDROOM RETURNS SHALL BE 1 AND 1 HALF TIMES THE CROSS | | | SECTIONAL AREA OF THE SUPPLY DUCT ENTERING THE ROOM AND | | | THE DOOR WILL NEED TO HAVE A 1 INCH UNDERCUT. |
|