| Date |
Text |
| 2022-12-09 10:33:01 | RENOVATION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR DOORS, WINDOWS AND |
| | ROOFING SYSTEM. ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD |
| | FBC WPB 107.3.4 |
| | |
| | 2) PLEASE SHOW THE ROOF SCUTTLE DISTANCE FROM EDGE OF |
| | ROOF OR GUARD RAILS PER FBC 1015.7 ROOF ACCESS. |
| | GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING |
| | IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR |
| | OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN |
| | SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE |
| | FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE |
| | CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 |
| | INCHES (533 MM) IN DIAMETER. |
| | |
| | 3) PLEASE SHOW THE ROOF TOP EQUIPMENT DISTANCE FROM THE |
| | EDGE OF THE ROOF - FBC 1015.6 MECHANICAL EQUIPMENT, |
| | SYSTEMS AND DEVICES. |
| | GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| | SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND |
| | EACH END OF SUCH COMPONENTS. THE GUARD SHALL BE |
| | CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 |
| | INCHES (533 MM) IN DIAMETER. |
| | |
| | 4) EXTERIOR DOORS ON THE SOUTH AND EAST SIDE OF THE |
| | BUILDING SHOULD NOT OPEN ON TO THE SIDE WALK - FBC |
| | 3202.2 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO |
| | THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 5) NOT A COMPLETE REVIEW -THE STRUCTURAL DRAWINGS ARE |
| | NOT IN PROJECTDOX. |
| | |